Viessmann · Boiler · Startup

Therm-Control low temperature protection during start-up

Vitorond 200 VD2A

What happens, in order

  1. Phase 1 if the set Therm-Control temperature is not reached at the sensor, the control stops the system pump and closes the mixing valve if fitted.
  2. Phase 1 the burner runs at full fire until the boiler minimum setpoint is reached.
  3. Phase 2 when the Therm-Control sensor passes the set temperature, the mixing valve opens and boiler flow is increased (example: 50%).
  4. As return temperature rises, the mixing valve opens further until full flow (100%) is reached.
  5. Once the setpoint is reached, the control modulates the burner firing rate and weather-responsive water temperature.

Applies to: Vitorond 200 VD2A with Vitotronic Therm-Control

Models

VD2A-125VD2A-160VD2A-195VD2A-230VD2A-270

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: vitorond 200 VD2A technical data manual, p. 15. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.