Viessmann · Boiler · Startup
Therm-Control low-temperature protection during start-up
What happens, in order
- Phase 1 The Therm-Control sensor has not reached its setpoint. The control shuts off the system pump, closes the mixing valve if fitted, and drives the burner to full fire.
- Phase 2 When the Therm-Control sensor exceeds its setpoint, the mixing valve opens and flow through the boiler increases (50% in the example).
- Phase 3 As return temperature rises, the mixing valve opens fully to 100% flow. The control then modulates the burner to meet the setpoint.
Applies to: Vitorond 200 VD2A with Vitotronic control
Models
VD2A-125VD2A-160VD2A-195VD2A-230VD2A-270
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2A installation instructions, p. 10. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.