Viessmann · Boiler · Standby/shutdown

System pump operation

Versatronik 300

What happens, in order

  1. Pump runs when outdoor temperature is below WWSD.
  2. If outdoor reset is not used, the pump runs whenever the common supply set point is above 0C/32F.
  3. After no set point is calculated, the pump keeps running for the factory delay before shutting off.
  4. The pump can be set to run continuously.

Timings and thresholds

ItemValue
Pump shutdown delay after no set point10 minutes (factory)

Applies to: Versatronik 300 pump output

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 300 Cascade Control manual, p. 30. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.