Viessmann · Boiler · Standby/shutdown
System pump operation
What happens, in order
- Pump runs when outdoor temperature is below WWSD.
- If outdoor reset is not used, the pump runs whenever the common supply set point is above 0C/32F.
- After no set point is calculated, the pump keeps running for the factory delay before shutting off.
- The pump can be set to run continuously.
Timings and thresholds
| Item | Value |
|---|---|
| Pump shutdown delay after no set point | 10 minutes (factory) |
Applies to: Versatronik 300 pump output
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 300 Cascade Control manual, p. 30. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.