Viessmann · Boiler · Heating
Supply temperature control differential
What happens, in order
- Single boiler with one mixing valve circuit: boiler water is held automatically 15°F (8 K) above the set supply temperature.
- Single boiler with a non-mixing and a mixing circuit: boiler water follows its own heating curve, with 15°F (8 K) above the mixing circuit supply set at the factory.
- Cascade with one mixing circuit common supply is held 15°F (8 K) above the mixing circuit set supply.
- Cascade with non-mixing and mixing circuits: common supply follows its own heating curve, with 15°F (8 K) above the mixing circuit set supply at the factory.
- Heating curve slope reference 1.8 for a non-mixing circuit, 1.2 for a mixing circuit.
Applies to: Single boiler and cascade control units
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW6B installation and service instructions, p. 79. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.