Viessmann · Boiler · Heating

Supply temperature control differential

Vitotronic 300 GW6B

What happens, in order

  1. Single boiler with one mixing valve circuit: boiler water is held automatically 15°F (8 K) above the set supply temperature.
  2. Single boiler with a non-mixing and a mixing circuit: boiler water follows its own heating curve, with 15°F (8 K) above the mixing circuit supply set at the factory.
  3. Cascade with one mixing circuit common supply is held 15°F (8 K) above the mixing circuit set supply.
  4. Cascade with non-mixing and mixing circuits: common supply follows its own heating curve, with 15°F (8 K) above the mixing circuit set supply at the factory.
  5. Heating curve slope reference 1.8 for a non-mixing circuit, 1.2 for a mixing circuit.

Applies to: Single boiler and cascade control units

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW6B installation and service instructions, p. 79. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.