Viessmann · Boiler · Standby/shutdown

Summer energy saving (heating pump logic)

Vitotronic 300

What happens, in order

  1. If outdoor temperature is above the preset room temperature setpoint, the heating circuit pump is switched off.
  2. When this happens the supply setpoint is set to 0°C / 32°F.
  3. The threshold can be selected via coding A5.
  4. Extended energy saving can also switch the pump off above the outdoor temperature set in coding A6, when the room setpoint is lowered via coding A9, or when a mixing valve has been closed for longer than the time set in coding A7.

Timings and thresholds

ItemValue
Mixing valve closed time before energy saving12 minutes

Applies to: Vitotronic 300 GW2

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 88. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.