Viessmann · Boiler · Standby/shutdown
Summer energy saving (heating circuit pump logic)
What happens, in order
- If the outdoor temperature is above the desired room temperature setpoint, the heating circuit pump switches off and the desired supply temperature is set to 32 F / 0 C.
- The switching threshold is set with coding A5.
- Extended summer energy saving can also switch the pump off when outdoor temperature exceeds the value set with coding A6.
- Extended summer energy saving can also switch the pump off when the desired room temperature is lowered with coding A9.
- With a mixing valve circuit, the pump can also switch off after the mixing valve has been closed for longer than the time set with coding A7.
Timings and thresholds
| Item | Value |
|---|---|
| Mixing valve closed before pump off (coding A7:1) | 20 minutes (text on p. 48 states 12 minutes) |
Applies to: Heating circuits in summer operation
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 KW2 service instructions, p. 48, p. 51. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.