Viessmann · Boiler · Standby/shutdown

Summer energy saving (heating circuit pump logic)

Vitotronic 300

What happens, in order

  1. If outdoor temperature is above the preset room set-point, switch off the heating circuit pump.
  2. In that case set the supply temperature set-point to 0°C / 32°F.
  3. Set the switching threshold via coding address A5 if needed.
  4. Extended summer saving can also switch the pump off above an outdoor temperature set in A6, or when the room set-point is lowered via A9.
  5. With a mixing valve circuit, the pump can also switch off after the mixing valve has been closed for more than 12 minutes (coding address A7).

Timings and thresholds

ItemValue
Mixing valve closed before pump off12 minutes (A7)

Applies to: Heating circuits

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 88. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.