Viessmann · Boiler · Startup

Starting the heating system

Vitodens 200-W

What happens, in order

  1. Check the system pressure on the gauge. If it is below 15 psi (1.0 bar), top up with water or call the heating contractor.
  2. For room-air dependent operation, make sure the boiler room ventilation openings are open and unobstructed.
  3. Open the gas shut-off valve.
  4. Switch on the power supply at the separate switch or fuse.
  5. Turn the ON/OFF switch to ON. The standard menu appears and the green ON indicator lights.
  6. Slide the black control cover outward to reach the ON/OFF switch.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Models

Vitodens 200-W B2HB 4557160199

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB service instructions, p. 31. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.