Viessmann · Boiler · Startup

Start-up wizard

Vitodens 200-W B2HB

What happens, in order

  1. Set the current time, then press OK to move to the date.
  2. Set the current date and press OK to finish.
  3. Select the language. The display starts in German, so choose the required language and press OK.
  4. Select the temperature unit (°C or °F) and press OK.
  5. Set the DHW temperature setpoint and press OK (only if a DHW sensor is installed).
  6. Choose the number of zone circuits and press OK. If none is selected, the control finishes setup and shows DHW/heating circuit 1, outdoor temperature, indoor temperature setup and burner status.
  7. For each zone circuit choose fixed setpoint or weather-compensated (with outdoor sensor) and press OK.
  8. For fixed setpoint, set the supply water temperature and press OK. For weather-compensated, adjust slope and shift and press OK.
  9. Assign the pump output for the zone circuit, confirm it, and press OK.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Models

B2HB 45B2HB 57B2HB 160B2HB 199

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HB 45, 57, 160, 199 service instructions, p. 12-14. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.