Viessmann · Boiler · Startup
Start-up wizard
What happens, in order
- Set the current time, then press OK to move to the date.
- Set the current date and press OK to finish.
- Select the language. The display starts in German, so choose the required language and press OK.
- Select the temperature unit (°C or °F) and press OK.
- Set the DHW temperature setpoint and press OK (only if a DHW sensor is installed).
- Choose the number of zone circuits and press OK. If none is selected, the control finishes setup and shows DHW/heating circuit 1, outdoor temperature, indoor temperature setup and burner status.
- For each zone circuit choose fixed setpoint or weather-compensated (with outdoor sensor) and press OK.
- For fixed setpoint, set the supply water temperature and press OK. For weather-compensated, adjust slope and shift and press OK.
- Assign the pump output for the zone circuit, confirm it, and press OK.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
Models
B2HB 45B2HB 57B2HB 160B2HB 199
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HB 45, 57, 160, 199 service instructions, p. 12-14. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.