Viessmann · Boiler · Startup

Start up the heating system

Vitocontrol-S

What happens, in order

  1. Check the system pressure on the manometer. If the needle is below the red marker, add water or call the heating contractor.
  2. Open the oil shut-off valves at the boiler, or open the gas shut-off valve.
  3. Switch on the power supply at the fuse or disconnect.
  4. Switch on the heating system on/off switch. The green lamp lights and the boiler temperature appears after a short time.

Applies to: Vitocontrol-S, VD2/CT3/CM2

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 14. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.