Viessmann · Boiler · Startup

Start-up cycle sequence

Vitodens 200-W B2HB

What happens, in order

  1. Control calls for heat.
  2. Fan starts up.
  3. Gas combination valve opens for ignition.
  4. Ignition takes place after a safety time.
  5. Ionization current builds and the burner runs.
  6. If the fan does not start correctly, fault F9 appears about 51 seconds after the call for heat.
  7. If ignition or flame fails, the burner faults with EE, E3 or EB as shown on the flow chart.

Timings and thresholds

ItemValue
Fault F9 after call for heatAbout 51 s
Reset after first-start air faultAbout 5 s

Codes you may see during this

F9 EE E3 EB

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Models

4557160199

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, pp. 20-21. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.