Viessmann · Boiler · Other

Slab curing (screed drying) program run

Versatronik 200

What happens, in order

  1. Enter the Slab curing prog level and select a day.
  2. Press F [OK] to activate the day, set the flow temperature, then press F [OK] to save.
  3. Repeat for each required day; enter '----' to end the program.
  4. Turn Slab curing to On to start the program.
  5. Controller holds the set flow temperature for each day at 00:00; the mixing valve circuits control to it while the boiler supplies it regardless of operating mode.
  6. After the program ends, the controller goes back to the selected operating mode.

Timings and thresholds

ItemValue
Program durationmaximum 28 days
Day change00:00 hrs
Setpoint range per day10°C to 60°C

Applies to: Versatronik 200 screed drying

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 installation and operating manual, p. 148. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.