Viessmann · Boiler · Standby/shutdown
Shutting down the boiler
What happens, in order
- Switch off the heating system on/off switch (item 8). The green lamp goes out and power to the boiler is cut.
- Close the gas shut-off valve (or the oil pipe shut-off valves at the boiler, whichever applies).
- Note with the boiler switched off there is no freeze-up protection for the boiler or DHW tank. Control unit settings are kept.
- For a temporary stop, use standby operation instead. For long shutdowns (several months), contact the heating contractor first.
Applies to: Vitotronic 100, GC1; in a multi-boiler system only the selected boiler is switched off at the control unit, the master control and power supply must be handled separately
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 operating instructions, p. 8. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.