Viessmann · Boiler · Standby/shutdown
Shut down the heating system
What happens, in order
- For a short time out of service, set the Vitocontrol-S to standby. To stop one boiler only, set standby on its Vitotronic 100.
- For long periods (several months), contact the heating contractor before and after shutdown for frost protection and heat exchanger protection.
- Switch off the heating system on/off switch on all control units. The green lamp goes out.
- Close the oil shut-off valves at the tank and filter, or close the gas shut-off valve.
- Switch off the main power supply. The system has no frost protection once power is off.
Applies to: Vitocontrol-S, VD2/CT3/CM2
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 14. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.