Viessmann · Boiler · Domestic hot water

Short-term operation of DHW recirculation pump

Switching Module-V

What happens, in order

  1. Close the potential-free contact at socket X3 (momentary button).
  2. The DHW recirculation pump runs for the time set at coding address 74.
  3. With a switch instead of a momentary button, the pump runs once for the set time.

Timings and thresholds

ItemValue
DHW recirculation pump run time (coding address 74)5 minutes at delivery

Applies to: Switching Module-V with Vitotronic 200 and 300

Models

7133 387

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Switching Module-V installation instructions, p. 3. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.