Viessmann · Boiler · Other
Set each boiler to constant temperature (cascade) mode
What happens, in order
- Turn on the boiler and set the language, then press OK.
- Set the time and date, then press OK.
- Press and hold OK until the service menu appears.
- Scroll to the service functions and press OK.
- Scroll to the multi-boiler system and press OK.
- Scroll to Yes and press OK. The boiler restarts in cascade mode.
- Set the language again and press OK.
- Repeat for each boiler, per the boiler installation instructions.
Applies to: Each boiler before cascade operation
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 and 300-K installation and service instructions, p. 12. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.