Return temperature protection (Circuit Diagram 13)
What happens, in order
- T1 temperature sensor measures the return temperature.
- Boiler control unit activates the return valve.
- Return valve keeps the return temperature from falling below the minimum value.
- Heating circuits with higher return temperature go to the top return connection; lower temperature circuits go to the bottom connection.
- Connect at least 15 % of the rated output take-off to the bottom return connection.
Applies to: Vitocrossal 300 lead boiler, Circuit Diagram 13
Models
Vitocrossal 300
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 32. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.