Viessmann · Boiler · Heating

Return temperature control and boiler supply temperature (Vitorond 200 as lag boiler)

Vitocontrol-S VD2/CT3/CM2Vitotronic 100 GC1

What happens, in order

  1. Temperature sensor T1 controls the isolation valve.
  2. Temperature sensor T2 switches the shunt pump.
  3. Return temperature control is done with the shunt pump and by closing the isolation valve.
  4. LON-BUS communication sets the boiler supply temperature automatically.
  5. The supply temperature is based on the highest required mixing valve circuit temperature plus an adjustable differential.

Applies to: Multi-boiler cascade with outdoor reset control

Models

Vitocrossal 200 CM2 (lead boiler)Vitorond 200 VD2 (lag boiler)

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100, GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 33. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.