Viessmann · Boiler · Heating
Return temperature control and boiler supply temperature (Vitorond 200 as lag boiler)
What happens, in order
- Temperature sensor T1 controls the isolation valve.
- Temperature sensor T2 switches the shunt pump.
- Return temperature control is done with the shunt pump and by closing the isolation valve.
- LON-BUS communication sets the boiler supply temperature automatically.
- The supply temperature is based on the highest required mixing valve circuit temperature plus an adjustable differential.
Applies to: Multi-boiler cascade with outdoor reset control
Models
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100, GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 33. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.