Reduced room temperature raised toward standard setting
What happens, in order
- During reduced room temperature operation, the control raises the reduced room setpoint based on outdoor temperature.
- The temperature rise follows the selected heating curve but never goes above the set standard room temperature.
- Outdoor temperature limits for the start and end of the raise are set in coding f8 and f9 in the Heating circuit group.
- When changing from reduced to standard room temperature, the boiler water or supply temperature is raised first, then the set boost is held for the set duration.
- The boost value and duration are set in coding fa and fb in the Heating circuit group.
Timings and thresholds
| Item | Value |
|---|---|
| Factory boost example | Boost to 146 F (60 C) (122 F / 50 C plus 20%) for 60 min |
Applies to: Vitotronic 300 GW6B heating circuit with reduced room temperature
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 300 GW6B installation and service manual, p. 80. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.