Viessmann · Boiler · Heating

Reduced room temperature raised toward standard setting

Vitotronic 300 GW6B

What happens, in order

  1. During reduced room temperature operation, the control raises the reduced room setpoint based on outdoor temperature.
  2. The temperature rise follows the selected heating curve but never goes above the set standard room temperature.
  3. Outdoor temperature limits for the start and end of the raise are set in coding f8 and f9 in the Heating circuit group.
  4. When changing from reduced to standard room temperature, the boiler water or supply temperature is raised first, then the set boost is held for the set duration.
  5. The boost value and duration are set in coding fa and fb in the Heating circuit group.

Timings and thresholds

ItemValue
Factory boost exampleBoost to 146 F (60 C) (122 F / 50 C plus 20%) for 60 min

Applies to: Vitotronic 300 GW6B heating circuit with reduced room temperature

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 300 GW6B installation and service manual, p. 80. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.