Raising the reduced room temperature by outdoor temperature
What happens, in order
- In reduced room temperature mode, the reduced setpoint rises with outdoor temperature along the heating curve.
- It never goes above the standard room setpoint.
- Set the outdoor temperature limits for the start and end of the raise in coding addresses F8 and F9.
Codes you may see during this
Applies to: Reduced room temperature operation
Models
B2HB 45B2HB 57B2HB 160B2HB 199
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB service manual, p. 90. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.