Viessmann · Boiler · Heating

Raising reduced room temperature and reducing heat-up time

Vitotronic 300 GW6B

What happens, in order

  1. During reduced room temperature operation, the reduced set point can be raised automatically following outdoor temperature, but never above the standard room set point. Start and end outdoor limits are set at f8 and f9.
  2. On transition from reduced to standard operation, boiler water or supply temperature is raised beyond the heating curve by the amount at coding fa, for the duration at coding fb.
  3. Example, factory settings heating curve value 122°F (50°C) raised by 20% gives 146°F (60°C) for 60 min.

Timings and thresholds

ItemValue
Heat-up boost duration (factory)60 min

Applies to: Heating circuits, time program changeover

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW6B installation and service instructions, p. 80. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.