Quick heat-up and quick setback (mixing circuits)

Vitotronic 300 GW6B

What happens, in order

  1. Quick heat-up raise the set room temperature by at least 4°F (2 K) by enabling comfort mode, switching from reduced to standard room temperature, or starting optimization (b7). Quick heat-up stops when the set room temperature is reached.
  2. Quick setback lower the set room temperature by at least 4°F (2 K) by enabling economy mode, switching from standard to reduced room temperature, or using shutdown time optimization (c1). Quick setback stops when the set room temperature is reached.
  3. Quick heat-up and setback only add influence when room temperature hook-up (b0) is used and the deviation is above 4°F (2 K). The influence can be raised at coding b6.

Applies to: Heating circuits with mixing valve and room sensor

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW6B installation and service instructions, p. 77. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.