Viessmann · Boiler · Other

Override mode (DHW time limit)

Versatronik 10.WB1

What happens, in order

  1. If the DHW demand lasts longer than the selected override timer, the unit enters override mode.
  2. The DHW pump output turns off and the boiler DHW call is cancelled.
  3. If a room thermostat call is present, the space heating pump runs.
  4. Override mode ends when the room thermostat call ends. DHW production then restarts if still called.

Timings and thresholds

ItemValue
Override timer (switch 3 ON)1/2 hour (switch 4 ON) or 1 hour (switch 4 OFF)

Applies to: Versatronik 10.WB1 with Vitodens 100-W WB1A/B

Models

Versatronik 10.WB1

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 10.WB1 installation and operating manual, pp. 22-23. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.