Viessmann · Boiler · Other
Override mode (DHW time limit)
What happens, in order
- If the DHW demand lasts longer than the selected override timer, the unit enters override mode.
- The DHW pump output turns off and the boiler DHW call is cancelled.
- If a room thermostat call is present, the space heating pump runs.
- Override mode ends when the room thermostat call ends. DHW production then restarts if still called.
Timings and thresholds
| Item | Value |
|---|---|
| Override timer (switch 3 ON) | 1/2 hour (switch 4 ON) or 1 hour (switch 4 OFF) |
Applies to: Versatronik 10.WB1 with Vitodens 100-W WB1A/B
Models
Versatronik 10.WB1
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 10.WB1 installation and operating manual, pp. 22-23. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.