Viessmann · Boiler · Freeze protection

Outdoor sensor frost protection

Versatronik 200

What happens, in order

  1. If outdoor temperature drops below the frost protection setting, the room setpoint for that circuit is set to 5 °C.
  2. The heating circuit is enabled, the pumps are switched on and a heat request is sent to the boiler.
  3. The function stops when the outdoor temperature rises 1 K above the frost protection setting.

Timings and thresholds

ItemValue
Stop point1 K above frost protection setting

Applies to: Versatronik 200 heating circuits

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 Installation and Operating Manual, p. 155. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.