Viessmann · Boiler · Heating

Normal mode (space heating)

Versatronik 10.WB1

What happens, in order

  1. The space heating pump runs whenever there is a room thermostat call (R-Stat) or 120 VAC control signal at the WB1 terminals.
  2. The DHW pump stays off in this mode.
  3. When a DHW call is sensed, the unit switches over to DHW mode.

Applies to: Versatronik 10.WB1 with Vitodens 100-W WB1A/B

Models

Versatronik 10.WB1

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 10.WB1 installation and operating manual, p. 22. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.