Mixing valve control (supply temperature)

Vitotronic 200

What happens, in order

  1. Do not move the mixing valve motor while the supply temperature is within the neutral zone of plus or minus 1.8 F / 1 C around the setpoint.
  2. If the supply temperature falls 1.8 F / 1 C below setpoint, the motor gets the open signal.
  3. If the supply temperature rises 1.8 F / 1 C above setpoint, the motor gets the close signal.
  4. The larger the control difference, the longer each signal lasts and the shorter the pauses between signals.
  5. On control restart, the mixing valve motor is driven closed and held closed for 150 seconds, then supply temperature control resumes.

Timings and thresholds

ItemValue
Neutral zoneplus or minus 1.8 F / 1 C around setpoint
Closed hold after control restart150 seconds

Applies to: Heating circuit with mixing valve

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 KW2 service instructions, p. 49. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.