Viessmann · Boiler · Heating
Mixing valve control (supply temperature)
What happens, in order
- Do not move the mixing valve motor while the supply temperature is within the neutral zone of plus or minus 1.8 F / 1 C around the setpoint.
- If the supply temperature falls 1.8 F / 1 C below setpoint, the motor gets the open signal.
- If the supply temperature rises 1.8 F / 1 C above setpoint, the motor gets the close signal.
- The larger the control difference, the longer each signal lasts and the shorter the pauses between signals.
- On control restart, the mixing valve motor is driven closed and held closed for 150 seconds, then supply temperature control resumes.
Timings and thresholds
| Item | Value |
|---|---|
| Neutral zone | plus or minus 1.8 F / 1 C around setpoint |
| Closed hold after control restart | 150 seconds |
Applies to: Heating circuit with mixing valve
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 KW2 service instructions, p. 49. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.