Viessmann · Boiler · Heating

Mixing valve control sequence

Vitotronic 300 GW6B

What happens, in order

  1. The mixing valve motor does not move inside the neutral zone of ±2°F (±1 K).
  2. If supply drops below set value by 2°F (1 K), the motor gets an open signal. Signal length grows with deviation and pauses get shorter.
  3. If supply rises above set value by 2°F (1 K), the motor gets a close signal. Signal length grows with deviation and pauses get shorter.

Timings and thresholds

ItemValue
Neutral zone±2°F (±1 K)

Applies to: Heating circuits with mixing valve (M2, M3)

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW6B installation and service instructions, p. 80. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.