Viessmann · Boiler · Heating
Mixing valve control sequence
What happens, in order
- The mixing valve motor does not move inside the neutral zone of ±2°F (±1 K).
- If supply drops below set value by 2°F (1 K), the motor gets an open signal. Signal length grows with deviation and pauses get shorter.
- If supply rises above set value by 2°F (1 K), the motor gets a close signal. Signal length grows with deviation and pauses get shorter.
Timings and thresholds
| Item | Value |
|---|---|
| Neutral zone | ±2°F (±1 K) |
Applies to: Heating circuits with mixing valve (M2, M3)
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW6B installation and service instructions, p. 80. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.