Mixing valve control in the heating circuit
What happens, in order
- Keep the mixing valve motor still while the supply temperature stays within the neutral zone of plus or minus 2 F (1 K) of the set value.
- If the supply temperature is more than 2 F (1 K) below set value, the mixing valve motor gets an open signal.
- If the supply temperature is more than 2 F (1 K) above set value, the mixing valve motor gets a close signal.
- The larger the control difference, the longer each signal pulse lasts and the shorter the pauses between pulses.
Timings and thresholds
| Item | Value |
|---|---|
| Neutral zone | +/-2 F (+/-1 K) around set supply temperature |
Applies to: Vitotronic 300 GW6B heating circuit with mixing valve
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 300 GW6B installation and service manual, p. 80. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.