Viessmann · Boiler · Heating
Mixing valve circuit control sequence
What happens, in order
- Do not drive the mixing valve motor inside the neutral zone (±1 K / ±2 °F).
- If supply temperature falls below set value (-1 K), the mixing valve motor receives the open signal.
- If supply temperature rises above set value (+1 K), the mixing valve motor receives the close signal.
- Larger control difference lengthens the signal duration and shortens the pauses between signals.
Applies to: Mixing valve heating circuits
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 132. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.