Viessmann · Boiler · Other
INT interlock operation
What happens, in order
- When interlock mode is enabled and INT is closed, the boiler plant may operate.
- If INT opens, the plant shuts down over communication and the display shows C1.
- When INT closes again, the fault clears and boilers restage.
- If the alarm option is set in coding, the Fault output turns on when INT is open and turns off when INT closes.
Codes you may see during this
Applies to: Versatronik 300 INT input
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 300 Cascade Control manual, p. 31. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.