Viessmann · Boiler · Domestic hot water

Hot water storage charging

Versatronik 200

What happens, in order

  1. Storage charging starts when the storage tank temperature drops 5 K below the setpoint.
  2. Hot water charging pump and burner run to heat the storage tank.
  3. Charging stops when the storage tank reaches the setpoint.

Timings and thresholds

ItemValue
Charging startStorage temperature 5 K below setpoint

Applies to: Versatronik 200 hot water

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 Installation and Operating Manual, p. 154. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.