Viessmann · Boiler · Domestic hot water
Heating the DHW primary tank from cold
What happens, in order
- If the DHW tank sensor reads below the set DHW temperature, the heating circuit pump starts and the three-way diverter valve changes over.
- The DHW tank primary pump starts when boiler water temperature is at or above the set DHW temperature.
- The burner starts when boiler water temperature is at or below the set DHW temperature. The DHW tank primary pump starts once the required boiler water temperature is reached.
- Heating stops when the set temperatures are reached at both the DHW tank sensor and the outlet sensor.
- After heating, the DHW tank primary pump and diverter valve stay on for a further 30 seconds.
Timings and thresholds
| Item | Value |
|---|---|
| DHW tank primary pump and three-way diverter valve run-on after heating | 30 sec |
Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125
Models
Vitodens 222-FB2TB 193568125
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 222-F B2TB service instructions, p. 35. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.