Viessmann · Boiler · Domestic hot water

Heating the DHW primary tank from cold

Vitodens 222-F

What happens, in order

  1. If the DHW tank sensor reads below the set DHW temperature, the heating circuit pump starts and the three-way diverter valve changes over.
  2. The DHW tank primary pump starts when boiler water temperature is at or above the set DHW temperature.
  3. The burner starts when boiler water temperature is at or below the set DHW temperature. The DHW tank primary pump starts once the required boiler water temperature is reached.
  4. Heating stops when the set temperatures are reached at both the DHW tank sensor and the outlet sensor.
  5. After heating, the DHW tank primary pump and diverter valve stay on for a further 30 seconds.

Timings and thresholds

ItemValue
DHW tank primary pump and three-way diverter valve run-on after heating30 sec

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Models

Vitodens 222-FB2TB 193568125

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 222-F B2TB service instructions, p. 35. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.