Viessmann · Boiler · Heating
Heating mode boiler water control
What happens, in order
- The control unit sets the boiler water temperature from outside temperature, or from room temperature if a room-temperature remote control is connected, and from the heating curve slope and shift.
- The calculated setpoint is sent to the burner control unit.
- The burner control unit compares set and actual boiler water temperature, calculates the modulation shift, and adjusts the burner.
- The electronic temperature limiter inside the burner control unit limits boiler water temperature.
Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125
Models
Vitodens 222-FB2TB 193568125
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 222-F B2TB service instructions, p. 35. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.