Viessmann · Boiler · Heating

Heating mode boiler water control

Vitodens 222-F

What happens, in order

  1. The control unit sets the boiler water temperature from outside temperature, or from room temperature if a room-temperature remote control is connected, and from the heating curve slope and shift.
  2. The calculated setpoint is sent to the burner control unit.
  3. The burner control unit compares set and actual boiler water temperature, calculates the modulation shift, and adjusts the burner.
  4. The electronic temperature limiter inside the burner control unit limits boiler water temperature.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Models

Vitodens 222-FB2TB 193568125

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 222-F B2TB service instructions, p. 35. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.