Viessmann · Boiler · Domestic hot water
Heating circuit response during DHW tank heating (priority control)
What happens, in order
- With priority control while the tank heats, the heating circuit supply setpoint is set to 32 F / 0 C, the mixing valve closes and the heating circuit pumps switch off.
- Without priority control the heating circuit continues to operate normally with its setpoint unchanged.
- With variable priority (mixing valve circuit only): the heating circuit pump stays on and the supply setpoint is lowered while the boiler water temperature is below its desired value. The amount depends on the boiler setpoint difference, outdoor temperature, heating curve slope and coding address A2.
Timings and thresholds
| Item | Value |
|---|---|
| Supply setpoint during priority control | 32 F / 0 C |
Applies to: Heating circuits during DHW tank heating
Models
Vitotronic 200 KW2
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 200 service instructions, p. 47. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.