Viessmann · Boiler · Standby/shutdown

Heating circuit pump economy shutdown

Vitotronic 200Vitotronic 300-K

What happens, in order

  1. Switch off the heating circuit pump and set supply temperature to 32°F (0°C) when outside temperature is above the economy limit (A5).
  2. In extended economy, switch the pump off when the adjusted outside temperature exceeds A6, when the room temperature exceeds B5, or when the calculated idle period after heating-to-reduced changeover runs.
  3. Confirm there is no frost risk and that B0 is set to 0 before using extended economy.
  4. Pump restarts early if heating mode is re-selected or the set room temperature is raised.

Timings and thresholds

ItemValue
Mixing valve closed before economy (A7)12 min
Pump idle periodSet via A9

Codes you may see during this

A5 A6 A9 B0 B5 A7

Applies to: Heating circuits

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 82. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.