Viessmann · Boiler · Standby/shutdown

Heating circuit pump economy shutdown

Vitotronic 300 GW6B

What happens, in order

  1. Pump switches off and supply is set to 32°F (0°C) if the outdoor temperature exceeds the value at coding a5.
  2. Pump switches off if the adjusted outdoor temperature exceeds the value at coding a6.
  3. Pump switches off if the mixing valve has tried to close for more than 12 min (coding a7).
  4. Pump switches off when the idle time at coding a9 has elapsed.
  5. Pump switches off if the actual room temperature exceeds the value at coding b5.
  6. Requirements no risk of frost, and coding b0 must be 0.
  7. If heating mode is selected or the room set point is raised during idle time, the pump restarts immediately.

Timings and thresholds

ItemValue
Mixing valve economy close attempt limit12 min

Applies to: Heating circuit pump economy function

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW6B installation and service instructions, p. 78. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.