Viessmann · Boiler · Standby/shutdown
Heating circuit pump economy shutdown
What happens, in order
- Pump switches off and supply is set to 32°F (0°C) if the outdoor temperature exceeds the value at coding a5.
- Pump switches off if the adjusted outdoor temperature exceeds the value at coding a6.
- Pump switches off if the mixing valve has tried to close for more than 12 min (coding a7).
- Pump switches off when the idle time at coding a9 has elapsed.
- Pump switches off if the actual room temperature exceeds the value at coding b5.
- Requirements no risk of frost, and coding b0 must be 0.
- If heating mode is selected or the room set point is raised during idle time, the pump restarts immediately.
Timings and thresholds
| Item | Value |
|---|---|
| Mixing valve economy close attempt limit | 12 min |
Applies to: Heating circuit pump economy function
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW6B installation and service instructions, p. 78. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.