Heating circuit control with mixing valve

Vitotronic 200Vitotronic 300-K

What happens, in order

  1. Calculate the set supply temperature from outside temperature, set room temperature, operating mode and heating curve slope and shift.
  2. Do not drive the mixing valve motor inside the neutral zone of ±1 K.
  3. If supply temperature drops 1 K below set value, send the mixing valve open signal.
  4. If supply temperature rises 1 K above set value, send the mixing valve closed signal.
  5. Longer control deviation lengthens the signal and shortens the pauses.
  6. Heating circuit without mixing valve follows the common system supply temperature; its pump is the only actuator.

Timings and thresholds

ItemValue
Neutral zone±1 K
Mixing valve closed for economy function12 min

Codes you may see during this

A7 B0 A5 A6 B5 A9

Applies to: Heating circuits with mixing valve

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 82-83. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.