Viessmann · Boiler · Heating
Heating circuit control with mixing valve
What happens, in order
- Calculate the set supply temperature from outside temperature, set room temperature, operating mode and heating curve slope and shift.
- Do not drive the mixing valve motor inside the neutral zone of ±1 K.
- If supply temperature drops 1 K below set value, send the mixing valve open signal.
- If supply temperature rises 1 K above set value, send the mixing valve closed signal.
- Longer control deviation lengthens the signal and shortens the pauses.
- Heating circuit without mixing valve follows the common system supply temperature; its pump is the only actuator.
Timings and thresholds
| Item | Value |
|---|---|
| Neutral zone | ±1 K |
| Mixing valve closed for economy function | 12 min |
Codes you may see during this
Applies to: Heating circuits with mixing valve
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 82-83. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.