Viessmann · Boiler · Freeze protection

Freeze-up protection activation and deactivation

Vitotronic 300

What happens, in order

  1. Outdoor temperature drops to the activation point.
  2. Freeze-up protection starts the circulation pumps.
  3. Boiler water is kept at the reduced setpoint, at a minimum of about 68 ºF (20 ºC); heating boilers with low limit hold their own minimum.
  4. When outdoor temperature rises above the deactivation point, the heating boiler and circulation pumps are switched off.

Timings and thresholds

ItemValue
Activation outdoor temperature34 ºF (1 ºC) or below
Deactivation outdoor temperatureAbove 37 ºF (3 ºC)
Minimum boiler water temperatureapprox. 68 ºF (20 ºC)

Applies to: Heating system freeze protection

Models

Vitotronic 300 Model KW3

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 technical data manual, p. 4. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.