Viessmann · Boiler · Freeze protection
Freeze-up protection activation and deactivation
What happens, in order
- Outdoor temperature drops to the activation point.
- Freeze-up protection starts the circulation pumps.
- Boiler water is kept at the reduced setpoint, at a minimum of about 68 ºF (20 ºC); heating boilers with low limit hold their own minimum.
- When outdoor temperature rises above the deactivation point, the heating boiler and circulation pumps are switched off.
Timings and thresholds
| Item | Value |
|---|---|
| Activation outdoor temperature | 34 ºF (1 ºC) or below |
| Deactivation outdoor temperature | Above 37 ºF (3 ºC) |
| Minimum boiler water temperature | approx. 68 ºF (20 ºC) |
Applies to: Heating system freeze protection
Models
Vitotronic 300 Model KW3
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 technical data manual, p. 4. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.