Viessmann · Boiler · Pump/purge

Fill program (control unit powered)

Vitodens 200-W

What happens, in order

  1. Set coding address 2F to 2 to start the circulation pump for filling.
  2. If the function is enabled, the burner shuts down during filling.
  3. Program turns off automatically after 20 minutes and 2F resets to 0.

Timings and thresholds

ItemValue
Program length20 minutes

Codes you may see during this

2F:2

Applies to: System filling

Models

B2HB 45B2HB 57B2HB 160B2HB 199

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB service manual, p. 90. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.