Viessmann · Boiler · Other
Emissions test function
What happens, in order
- In multi boiler systems, enable the emissions test function on all control units.
- The burner starts and all pumps start. In lag boiler control only the heating circuit pump starts.
- The mixing valve stays in its control function.
- For a test under 30 minutes, the burner runs at 100% until the burner control unit temperature limiter switches it off, then cycles at 100% around the limiter value.
- For a test over 30 minutes, the boiler water runs at its maximum set value (e.g. 194 F / 90 C) and the burner works in modulating mode to avoid excessive cycling.
Timings and thresholds
| Item | Value |
|---|---|
| Test duration under 30 minutes | Burner at 100% output until temperature limiter responds |
| Test duration over 30 minutes | Boiler water at max set value, e.g. 194 F (90 C), modulating |
Applies to: Multi boiler and single boiler systems
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300, GW6B installation and service instructions, p. 72. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.