Viessmann · Boiler · Other

Emissions test function

Vitotronic 300, GW6B

What happens, in order

  1. In multi boiler systems, enable the emissions test function on all control units.
  2. The burner starts and all pumps start. In lag boiler control only the heating circuit pump starts.
  3. The mixing valve stays in its control function.
  4. For a test under 30 minutes, the burner runs at 100% until the burner control unit temperature limiter switches it off, then cycles at 100% around the limiter value.
  5. For a test over 30 minutes, the boiler water runs at its maximum set value (e.g. 194 F / 90 C) and the burner works in modulating mode to avoid excessive cycling.

Timings and thresholds

ItemValue
Test duration under 30 minutesBurner at 100% output until temperature limiter responds
Test duration over 30 minutesBoiler water at max set value, e.g. 194 F (90 C), modulating

Applies to: Multi boiler and single boiler systems

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300, GW6B installation and service instructions, p. 72. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.