Viessmann · Boiler · Other
Emergency cooling via consumer circuits
What happens, in order
- Boiler temp reduct must be On.
- When any heat generator reaches Cool start t, the heating circuits start at supply temperature max (where allowed).
- Emergency cooling ends when the temperature falls 5 K below Cool start t.
Timings and thresholds
| Item | Value |
|---|---|
| Cool start t | 30°C - 120°C, standard 95°C |
| Emergency cooling end | 5 K below Cool start t |
Applies to: Versatronik 200, first boiler and solid fuel boiler
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 200 installation and operating manual, p. 140. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.