Viessmann · Boiler · Other
Emergency cooling (Service mode)
What happens, in order
- Select Service mode (W) on the controller.
- The heat generator regulates to its maximum temperature.
- When the heat generator reaches 65 C, the consumer circuits are driven to their maximum flow temperature to dump heat.
- Confirm the B-Heat sink set value is enabled in each consumer circuit, otherwise this function does not run.
- Service mode resets automatically after 15 minutes.
Timings and thresholds
| Item | Value |
|---|---|
| Service mode automatic reset | 15 min |
Applies to: Versatronik 200 System Control with consumer circuits
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 200 manual, p. 68. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.