Emergency cooling (Service mode)

Versatronik 200

What happens, in order

  1. Select Service mode (W) on the controller.
  2. The heat generator regulates to its maximum temperature.
  3. When the heat generator reaches 65 C, the consumer circuits are driven to their maximum flow temperature to dump heat.
  4. Confirm the B-Heat sink set value is enabled in each consumer circuit, otherwise this function does not run.
  5. Service mode resets automatically after 15 minutes.

Timings and thresholds

ItemValue
Service mode automatic reset15 min

Applies to: Versatronik 200 System Control with consumer circuits

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 manual, p. 68. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.