Viessmann · Boiler · Domestic hot water

DHW tank temperature control sequence

Vitotronic 300

What happens, in order

  1. When DHW tank temperature falls 2.5°C / 4.5°F below set-point (adjustable via coding 59), set boiler water 20 K above the DHW set-point (coding 60).
  2. Start the DHW tank loading pump. With coding 61:01 it starts immediately; with 61:00 it starts when boiler water is 7°C / 13°F above DHW temperature.
  3. With priority control (A2:2), set supply set-point to 0°C / 32°F, close the mixing valve and switch off the heating circuit pump while heating DHW.
  4. Without priority control, the heating circuit keeps running with set-point unchanged.
  5. With modulating priority (mixing valve circuit only), keep the heating circuit pump on and lower the supply set-point until boiler water reaches its target.
  6. When DHW reaches set-point +2.5°C / 4.5°F, return boiler water to weather-compensated set-point.
  7. Keep the DHW pump running until boiler-to-DHW difference is under 7°C / 13°F, or boiler reaches its weather-compensated target, or DHW exceeds set-point by 5°C / 9°F, or run-on time ends.
  8. With optimized DHW heating (55:1), the control sets burner and pump switch-off so DHW does not overshoot much.

Timings and thresholds

ItemValue
Boiler set-point above DHW set-point20 K (coding 60)
DHW pump start threshold (boiler temp dependent)7°C / 13°F
DHW pump max run-on15 minutes (coding 62)
DHW overshoot stop5°C / 9°F
DHW switching differential±2.5°C / 4.5°F

Applies to: DHW tank

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 90-91. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.