Viessmann · Boiler · Domestic hot water
DHW tank heating with two tank sensors (coding 55:2)
What happens, in order
- Sensor 1 enables the DHW pump and is checked for stop conditions during pump delay off.
- Sensor 2 makes tank heating start early when a lot of hot water is drawn and end early when little is drawn.
- Start heating when sensor 1 or the sensor 2 start point is reached: set DHW temperature -5 F (-2.5 K) or actual temperature at sensor 2 below set DHW temperature times the start factor (coding 69).
- Stop heating when the tank is hot set value +5 F (+2.5 K) and sensor 2 above set DHW temperature times the stop factor (coding 68).
Applies to: Single boiler or cascade with two DHW sensors, coding 55:2
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 300 GW6B installation and service manual, p. 82. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.