Viessmann · Boiler · Domestic hot water

DHW tank heating with two DHW sensors (code 55:2)

Vitotronic 200Vitotronic 300-K

What happens, in order

  1. Sensor 1 enables the DHW circulation pump and is checked for stop conditions during run-on.
  2. Sensor 2 starts heating early when a lot of hot water is drawn and stops it early when none is drawn.
  3. Start heating when the tank is cold (set value −2.5 K) or when sensor 2 is below set DHW temperature times the start factor (code 69).
  4. Stop heating when the tank is hot (set value +2.5 K) and sensor 2 is above set DHW temperature times the stop factor (code 68).

Timings and thresholds

ItemValue
Start/stop switching differential±2.5 K

Codes you may see during this

55:2; 68; 69

Applies to: DHW tanks with two sensors

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 86. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.