Viessmann · Boiler · Domestic hot water

DHW tank heating with tank loading system in cascade (coding 55:3)

Vitotronic 300 GW6B

What happens, in order

  1. When the tank cools, start the primary pump in the tank loading system and set the common supply temperature 36 F (20 K) above set DHW temperature.
  2. Open the 3-way mixing valve and regulate it to set value.
  3. The tank loading circulation pump cycles until the supply reaches set DHW temperature plus 9 F (5 K), then runs continuously.
  4. When the tank is hot, return the common supply to the weather-compensated value.
  5. The DHW pump stops at once when the 3-way valve is fully open, or after the delay off time set at coding 62.

Timings and thresholds

ItemValue
Tank cold triggerSet DHW temperature -5 F (-2.5 K), change at coding 59
Tank hot sensor 2 limitSet value -3 F (-1.5 K)

Applies to: Cascade with tank loading system, coding 55:3

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 300 GW6B installation and service manual, p. 84. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.