Viessmann · Boiler · Domestic hot water

DHW tank heating with priority control

Vitotronic 300

What happens, in order

  1. When the DHW tank heats, the boiler setpoint becomes 20°C / 36°F above the desired DHW tank temperature (changeable via coding 60).
  2. With priority control, the heating circuit supply setpoint is set to 0°C / 32°F.
  3. With priority control, the heating circuit pump is switched off.
  4. With modulating priority (mixing valve circuit only), the heating pump stays on and the supply setpoint is lowered until the boiler setpoint is reached.

Codes you may see during this

50 51 58 59

Applies to: Vitotronic 300 GW2

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 86-87. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.