Viessmann · Boiler · Domestic hot water
DHW tank heating with gas-fired space heating boiler
What happens, in order
- Tank DHW heating starts when tank temperature is 4.5°F (2.5°C) below the tank setpoint.
- The burner and tank DHW pump switch on.
- Factory default boiler water target is 36°F (20°C) above the tank setpoint.
- When tank temperature reaches 4.5°F (2.5°C) above the tank setpoint, the burner switches off.
- The tank DHW pump then runs its time delay function.
Timings and thresholds
| Item | Value |
|---|---|
| DHW heating start | 4.5°F (2.5°C) below tank setpoint |
| Boiler water target above tank setpoint (factory default) | 36°F (20°C) |
| DHW burner shutoff | 4.5°F (2.5°C) above tank setpoint |
Applies to: Vitodens 200-W B2HB with DHW tank
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 33. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.