Viessmann · Boiler · Domestic hot water

DHW tank heating with gas-fired space heating boiler

Vitodens 200-W B2HB

What happens, in order

  1. Tank DHW heating starts when tank temperature is 4.5°F (2.5°C) below the tank setpoint.
  2. The burner and tank DHW pump switch on.
  3. Factory default boiler water target is 36°F (20°C) above the tank setpoint.
  4. When tank temperature reaches 4.5°F (2.5°C) above the tank setpoint, the burner switches off.
  5. The tank DHW pump then runs its time delay function.

Timings and thresholds

ItemValue
DHW heating start4.5°F (2.5°C) below tank setpoint
Boiler water target above tank setpoint (factory default)36°F (20°C)
DHW burner shutoff4.5°F (2.5°C) above tank setpoint

Applies to: Vitodens 200-W B2HB with DHW tank

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 33. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.