Viessmann · Boiler · Domestic hot water
DHW tank heating via tank loading system (coding 55:3)
What happens, in order
- When the tank cools, start the primary pump in the tank loading system.
- Open the 3-way mixing valve and regulate it to the set value.
- The DHW pump cycles on and off until the supply reaches set DHW temperature plus 10 F (5 K), then runs continuously.
- If the temperature drops during heating, the DHW pump cycles again.
- When the tank is hot (sensor 1 at or above set value, sensor 2 above set value -3 F (-1.5 K)), return the boiler water setpoint to the weather-compensated value.
- The DHW pump stops at once when the 3-way valve is fully open, or after the delay off time set at coding 62.
Timings and thresholds
| Item | Value |
|---|---|
| Tank cold trigger | Set DHW temperature -5 F (-2.5 K), change at coding 59 |
| Supply setpoint during tank heating | Set DHW temperature +10 F (+5 K), boiler setpoint +36 F (+20 K) |
| Tank hot sensor 2 limit | Set value -3 F (-1.5 K) |
Applies to: Tank loading system, coding 55:3, single boiler
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 300 GW6B installation and service manual, p. 83. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.