Viessmann · Boiler · Domestic hot water
DHW tank heating, standard control (code 55:0)
What happens, in order
- When the DHW tank goes cold, set the common supply temperature 20 K above the set DHW temperature.
- When the tank is hot, return the supply temperature to the weather-compensated value.
- Let the circulation pump run on after heating until the weather-compensated supply temperature is reached, the DHW temperature is exceeded by 5 K, or the max run-on time expires.
- With code 62:0 there is no pump run-on.
Timings and thresholds
| Item | Value |
|---|---|
| Switching differential | ±2.5 K |
| Supply temp above set DHW temp | 20 K |
| Automatic mode DHW start ahead of heating circuit | 30 min |
| Max pump run-on | Set via code 62 |
Codes you may see during this
55:0; 59; 60; 62
Applies to: DHW tanks
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 85-86. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.