Viessmann · Boiler · Domestic hot water

DHW tank heating, standard control (code 55:0)

Vitotronic 200Vitotronic 300-K

What happens, in order

  1. When the DHW tank goes cold, set the common supply temperature 20 K above the set DHW temperature.
  2. When the tank is hot, return the supply temperature to the weather-compensated value.
  3. Let the circulation pump run on after heating until the weather-compensated supply temperature is reached, the DHW temperature is exceeded by 5 K, or the max run-on time expires.
  4. With code 62:0 there is no pump run-on.

Timings and thresholds

ItemValue
Switching differential±2.5 K
Supply temp above set DHW temp20 K
Automatic mode DHW start ahead of heating circuit30 min
Max pump run-onSet via code 62

Codes you may see during this

55:0; 59; 60; 62

Applies to: DHW tanks

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 85-86. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.